Is Your Team Checking Fire Safety Devices Every Month?

Simple routines your maintenance staff can follow between scheduled professional inspections

Some fire and life safety deficiencies in an occupied building start small. A misplaced piece of luggage might bump a pull station in a hotel hallway, or an exit sign battery can gradually lose its charge over time. When these small deficiencies go unnoticed, they are usually only caught during your next formal service visit, months after they first occurred. 

Scheduled inspection and testing work are the foundation of a reliable fire alarm system. Between those visits, your maintenance team walks the property daily and sits in the best position to spot changes early. A structured set of monthly checks helps turn that daily familiarity into a practical routine. Read on to see how local property and maintenance teams in Hawaii can set up a straightforward monthly walk-through.

Start With the Push-to-Test Devices

A practical starting point includes the equipment your team can verify directly using a built-in test button. Standalone smoke alarms operate independently of your main fire alarm system. Property teams should test these units monthly or following the manufacturer’s instructions. For most smoke alarms, press and hold the test button until the audible signal sounds, and resolve any low-battery chirps or failed tests immediately. Smoke detectors connected to building fire alarm systems should remain as part of your provider’s inspection and testing schedule. 

Battery-backed exit signs and emergency lighting fixtures require similar attention. NFPA 101 calls for a functional test lasting at least 30 seconds each month, along with an annual 90-minute test. Press the test button on each fixture to confirm it illuminates under battery power. For self-testing units, your staff can check the status indicator lights during routine passes. 

Look Over Every Portable Fire Extinguisher

NFPA 10 sets the inspection interval for portable fire extinguishers at no more than 31 days, which translates to a monthly visual inspection. The purpose is to confirm that each extinguisher is in its designated location and appears ready for use. 

Verify that every extinguisher sits in its designated cabinet or bracket without any obstructions blocking access. Check that the pull pin and plastic tamper seal remain intact, as a broken seal may indicate someone may have used or tampered with the unit. If the extinguisher is equipped with a pressure gauge, confirm that the needle rests in the green operable range, and look over the cylinder for any physical damage or corrosion. The Honolulu Fire Department publishes a monthly extinguisher checklist that your staff can download for reference. 

Walk the Property to Spot Physical DamageĀ 

Because maintenance staff see the same hallways and rooms every day, physical changes can easily blend into the background. Setting aside time once a month for a visual walk-through helps staff focus specifically on device conditions. 

Physical damage typically occurs during everyday operations. During your walk-through, look for key visual indicators: 

  • Fire alarm field devices such as pull stations, smoke and heat detectors, horn/strobes, and speaker/strobes that are damaged, loose, painted over, obstructed, covered, or otherwise visibly compromised
  • Devices exposed to the elements showing signs of water intrusion, condensation, corrosion, insects, rodents, bird activity, or debris that could interfere with operation or visibility
  • Fire alarm panels and annunciators with visible damage, open or damaged enclosures, water intrusion, or abnormal trouble or supervisory indications
  • Exit signs, emergency lighting, and fire extinguishers that are damaged, obstructed, missing, displaced, or otherwise visibly out of normal condition

Keep this walk strictly visual. Leave the system components in place and log any findings so a trained fire alarm service provider can evaluate the necessary repairs. 

Keep a Monthly Log

A monthly tracking log helps staff document each check consistently. A binder or digital log works well for recording the date, location, results, and staff initials for each inspected device or equipment item. Any identified issues can be listed on a separate line alongside the corresponding repair actions.

Clear documentation maintains internal accountability and provides useful background information for your fire alarm service provider during their next scheduled visit. These internal records complement the digital reports and device-level testing results generated during your professional inspections. Implementing a standardized checklist gives your staff a straightforward template to follow. Download our Monthly Fire & Life Safety Checklist to get your team started.

Keeping Your Fire Alarm System Reliable Between Visits

Monthly checks give your team a clear, actionable role in supporting property safety between professional service visits. Catching physical changes early helps resolve minor items before they lead to larger repairs or inspection deficiencies. 

If your team identifies damaged equipment during a walk-through, contact Phoenix Pacific to speak with a representative about the appropriate next steps.